Complete matrix formulation of fault-position method for voltage-dip characterisation

handle: 11588/101989 , 11367/25540 , 11580/13174
The method of fault position is useful for characterising power-system performance in the presence of voltage dips due to faults. It is based on short-circuit simulations repeated for all the system nodes and for many points along the system lines: fault voltages that are below a preset threshold are the required voltage dips. These dips are stored in so-called dip matrices which contain only the dips in all the system nodes when faults occur at points along the lines. The paper proposes a new compact analytical formulation of dip matrices for balanced and unbalanced faults in terms of bidimensional vector relations and for site- and system-voltage dip indexes. Compact formulations are very useful tools when several sensitivity analyses have to be conducted to estimate variation of site- and system-voltage dip indexes in relation to possible reinforcement and/or compensation devices. Graphical presentation of dip matrices is also proposed as a valuable tool to ascertain the critical area for system performance. Numerical applications to an actual transmission system are presented to demonstrate the easy applicability of the model.
Power distribution; power quality (PQ); power system reliability; power transmission; voltage dips.
Power distribution; power quality (PQ); power system reliability; power transmission; voltage dips.
citations This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).31 popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network.Top 10% influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).Top 10% impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network.Average