Study on the Maximum Ice-Shedding Height of Conductor Based on Energy Method

Ice shedding of transmission lines may lead to interphase flashover and thereby endanger power transmission. The ice shedding of transmission lines is essentially an energy conversion process. Based on the vibration theory and energy method of cable structures, the iced load of a transmission line is regarded as the working load under the condition of a bare conductor. The theoretical analysis model of ice shedding for a single-span transmission line was established with a vertical symmetrical vibration mode configuration. Then the analytical solution of maximum jump height is given. The proposed formula makes clear the quantitative relationship among maximum jump height and the verticality of the conductor, the icing mass ratios, and the dimensionless frequency. The vibration of a single-span transmission line after ice shedding is investigated by the finite element method to validate the proposed formula. The results show that the maximum jump height calculated by the formula has a good agreement with the finite element analysis, which fully meets the engineering accuracy requirements. The total jump height calculated by the current method is only 1.6% lower than that from finite element method. The contribution of high-order vertical mode is small with a small sag. By considering the contribution of high-order vertical modes, the calculation formula was further modified to get more accurate results. Since the vertical modes are mainly determined by dimensionless parameters, a simplified calculation empirical formula for maximum jump height optimization was obtained by fitting based on parametric analysis results. The presented proposed formula can provide theoretical guidance and be employed to predict the maximum jump height after ice shedding for transmission line design.
- State Grid Hebei Electric Power Company China (People's Republic of)
- State Grid Shanxi Electric Power Company (China) China (People's Republic of)
- State Grid Shanxi Electric Power Company (China) China (People's Republic of)
- CHINA ELECTRIC POWER RESEARCH INSTITUTE (SEAL) SOE China (People's Republic of)
- Electric Power Research Institute United States
ice shedding, Transmission line, maximum jump height, energy method, analytical formula, Electrical engineering. Electronics. Nuclear engineering, TK1-9971
ice shedding, Transmission line, maximum jump height, energy method, analytical formula, Electrical engineering. Electronics. Nuclear engineering, TK1-9971
citations This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).0 popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network.Average influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).Average impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network.Average