Calibration Proposal for UHF Partial Discharge Measurements at Power Transformers

doi: 10.3390/en12163058
The continuous, non-intermitted service of electrical grids relies on the reliability of their assets, e.g., power transformers. Local insulation defects can result in serve failures such as breakdowns with severe subsequent costs. The prevention of such events is crucial. Hence, partial discharge (PD) activity at power transformers is evaluated directly in the factory before shipment. Additionally, PD activity can be monitored during service using the ultra-high frequency (UHF) method. In this contribution, a calibration procedure is proposed for the UHF method. The calibration process is required to ensure both, reproducibility and comparability of UHF measurements: Only a calibrated UHF measurement procedure can be introduced supplementary to IEC 60270 in acceptance tests of power transformers. The proposed calibration method considers two factors: The influence of the UHF-antenna’s sensitivity and the PD recorder characteristics including accessories such as cable damping, pre-amplifier, etc. The former is addressed by a characterization of UHF sensors using the standard antenna factor (AF) in a gigahertz transverse electromagnetic (GTEM) cell. The PD recorder’s influence is corrected by using a defined, invariable test signal as reference for all recording devices. A practical evaluation of the proposed calibration procedure is performed in a laboratory setup using different UHF recording devices and UHF sensors using artificial PD signals and real voltage-driven PD sources.
- Siemens (Germany) Germany
- University of Stuttgart Germany
- Siemens (Germany) Germany
- Karlsruhe University of Applied Sciences Germany
- Karlsruhe University of Applied Sciences Germany
Technology, T, power transformers; partial discharge; PD; UHF; calibration; monitoring; acceptance tests; IEC 60270; PD sensors; antenna factor, calibration, UHF, power transformers, antenna factor, partial discharge, monitoring, acceptance tests, PD, PD sensors, IEC 60270
Technology, T, power transformers; partial discharge; PD; UHF; calibration; monitoring; acceptance tests; IEC 60270; PD sensors; antenna factor, calibration, UHF, power transformers, antenna factor, partial discharge, monitoring, acceptance tests, PD, PD sensors, IEC 60270
citations This is an alternative to the "Influence" indicator, which also reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).29 popularity This indicator reflects the "current" impact/attention (the "hype") of an article in the research community at large, based on the underlying citation network.Top 10% influence This indicator reflects the overall/total impact of an article in the research community at large, based on the underlying citation network (diachronically).Top 10% impulse This indicator reflects the initial momentum of an article directly after its publication, based on the underlying citation network.Top 10%